43-63150SH**
Three Phase – General Purpose

Primary Volts 480 Delta
Secondary Volts 208Y / 120, 60 Hz

May be used on a 480Y / 277 Volt Supply

KVA Capacity:  150.00
Weight/Lbs.:  1255.00
Taps:  6
Max Amps Primary:  180
Max Amps Secondary: 361
Height A: 41.00″
Width B: 34.25″
Depth C: 26.75″
Use Connection Diagram 6 – Click Here

SKU: 43-62150SH Category:
  • Copper windings up to 9kva.
  • Aluminum windings on 15kva and larger.
  • UL Class 180°C  or 220°C insulation system.
  • NEMA Type 3R, enclosure suitable for indoor or outdoor applications.
  • No extra rainshields required for outdoor use.
  • Multiple knockouts provide convenient conduit entry and exit locations through the side and back of the wiring compartment.
  • Ground studs provided for bonding compatibility with both metallic and nonmetallic conduit.
  • ** Meets DOE TP-1 requirements